Beamline Critical Devices

L:RFQ

Control Device : L:CRDEV

Areas Protected : Linac Enclosure

Test Procedure

1. Call up digital status for L:CRDEV.

2. Turn on the Low Level RF Amplifier Power Supply L:RFQ by issuing an on command via the digital status page to the critical device controller.

3. Verify the digital status for L:CRDEV indicates the Low Level RF Amplifier Power Supply L:RFQ is on.

4. Issue an off command from the digital status page to the critical device controller.

5. Verify the digital status for L:CRDEV indicates the Low Level RF Amplifier Power Supply L:RFQ turns off.

6. Document the results in the MCR Logbook.