Beamline Critical Devices

F:MW1W

Control Device : F:MTPCDC

Areas Protected : MT6-1 & MT6-2

Test Procedure

1. Call up digital status for F:MTPCDC.

2. Turn on F:MW1W via a parameter page.

3. Verify the digital status for F:MTPCDC indicates the power supply is ready and on.

4. Issue an off command from the digital status page to the critical device controller.

5. Verify the digital status for F:MTPCDC indicates the power supply is off.

6. Document the results in the MCR Logbook.